Lilly Grove Special Utility District

2017 Consumer Confidence Report for Public Water System LILLY GROVE SUD


Regulated Contaminant


Disinfection and                   Collection       Highest Level          Range of Level       
Disinfection By-Products         Date               Detected                  Detected            MCLG        MCL    Units    Violation   Likely Source of Contamination  
Haloacetic Acids                       2017                   13                      13.3 - 17.3       No goal for    60       ppb         NO         By-Product of drinking water  
(HAA5)                                                                                                                       the total                                                   chlorination.    


Not all samples results may have used for calculating highest level detected because some results may be part of an evaluation to
determine where compliance sampling should occur in the future


Total Trihalomethanes             2017                   42                       41.2 - 41.2       No goal for    80       ppb         NO        By-Product of drinking water  
(TThm)*                                                                                                                        the total                                                   chlorination.    


Not all sample results may have been used for calculating the Highest Level Detected because some results may be part of an evaluation to   
determine where compliance sampling should occur in the future


                                                     Collection        Highest Level           Range of Level      

 Inorganic Contaminants         Date                 Detected                   Detected               MCLG       MCL    Units     Violation   Likely Source of Contamination
Antimony                                  3/4/2009      Levels lower than           0 - 0                        6                6         ppb            NO        Discharge from petroleum re-  
                                                                               detect Level                                                                                                                   fineries; fire retardants; ceramic  
                                                                                                                                                                                                                        electronics; solder; test addition  
Arsenic                                      3/4/2009       Levels lower than          0 - 0                         0               10         ppb           NO        Erosion of natural deposits;  
                                                                              detect Level                                                                                                                    Runoffs from orchards, glass and   
                                                                                                                                                                                                                        electronics production waste.  
Barium                                     12/2/2016              0.037                 0.037 - 0.037                  2                2          ppm          NO         Discharge of drilling wastes;   
                                                                                                                                                                                                                         Discharge from metal refineries;  
                                                                                                                                                                                                                         Erosion of natural deposits;  
Beryllium                                 3/4/2009     Levels lower than            0 - 0                        4                 4          ppb            NO         Discharge from metal refineries;  
                                                                            detect Level                                                                                                                       and coal-burning factories; Discharge  
                                                                                                                                                                                                                         from electrical, aerospace, and defense  
Cadmin                                    3/4/2009     Levels lower than             0 - 0                        5                 5           ppb           NO         Corrosion of galvanized pipes; Erosion  
                                                                           detect Level                                                                                                                        of natural deposits; Discharge from  
                                                                                                                                                                                                                          metal refineries; runoff from batteries  
Chromium                              3/4/2009     Levels lower than            0 - 0                     100             100          ppb            NO        Discharge from steel and pulp mills;  
                                                                          detect Level                                                                                                                         Erosion of natural deposits.                           
Cyanide                                   6/9/2011      Levels lower than             0 - 0                    200             200         ppb            NO        Discharge from plastic and fertilizer  
                                                                             detect Level                                                                                                                      factories; Discharge from steel/metal  
                                                                                                                                                                                                                          factories;     
Fluoride                                   7/7/2009              0.074                          0.074                      4                  4            ppm          NO         Erosion of natural deposits; Water

                                                                                                                                                                                                                         additive which promotes strong teeth;
                                                                                                                                                                                                                         Discharge from fertilizer and aluminum  
Mercury                                 3/4/2009       Levels lower than            0.095                     2                  2             ppm         NO        Erosion of natural deposits; Discharge from
                                                                            detect Level                                                                                                                       refiners and factories; Runoffs from   
                                                                                                                                                                                                                         landfills and cropland  
Nitrate                                  2017 0.029        0.0113 - 0.029                   10                        10                                ppm         NO         Runoff from fertilizer use; Leaching from  
(Measured as Nitrogen)                                                                                                                                                                               Septic tanks, sewage; Erosion of natural  
                                                                                                                                                                                                                         deposits    


Nitrate Advisory - Nitrate in drinking water at levels above 10 ppm is a health risk for infants of less than six months of age High nitrate levels in drinking 
water can cause blue baby syndrome. Nitrate levels may rise quickly for short periods of time because of rainfall or agricultural activity. If you are caring  
for a infant you should ask advise from your health care provider.